DIP switches of the T/H sensor are incorrectly set.
The T/H sensor is faulty.
Procedure
Step 1
Tap
Settings
>
System Settings
>
T/H Sensor
to check whether the T/H sensor is enabled on
the controller.
If it is disabled, change it to enabled and check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 2
.
If it is enabled, go to
Step 2
.
Step 2
Check whether DIP switches of the T/H sensor is set correctly by referring to
3.8.6 Installing
T/H Sensors
.
If no, set it correctly by referring to
3.8.6 Installing T/H Sensors
and check whether the
fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 3
.
If yes, go to
Step 3
.
Step 3
Check whether the T/H sensor is faulty.
If yes, replace it by referring to
5.6.9 Replacing an T/H Sensor
and check whether the
fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 4
.
If no, go to
Step 4
.
Step 4
Contact Huawei technical support.
----End
5.5.9 The LCD does not Light
Symptom
The LCD does not light when powering on.
Possible Causes
Main control board circuit breaker QF5 is not switched on.
The transformer fuse is blown.
The transformer is faulty.
The main control board is faulty.
The LCD connection is abnormal.
The LCD is faulty.