NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
Support Preparations
A support is optional for the air conditioner. You can configure a support in the following two
ways:
Prepare the support according to the drawings obtained from Huawei.
Specify the support as a mandatory item for the air conditioner in the contract.
Adjust the height of the support according to the actual situation.
Figure 3-5
shows the support
dimensions for reference.
Figure 3-5
shows the support dimensions of the air conditioner which installed the
enclosure increasing the depth to 1200 mm.
If not configured the enclosure. The size of the depth 1143 mm and 1200 mm all subtract
200 mm when making support.
Figure 3-5
Support dimensions (unit: mm)
Make supports by referring the following recommendations:
1.
Recommended to use angle steel, square steel or channel steel, and width is 45–60 mm,
thickness is 4–5 mm.