5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
83
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
overfreq
is
generated,
and the
system
shuts down.
unstable.
2.
The surge protection and
voltage test board is
faulty.
2.
Replace the surge
protection and voltage
test board.
a035
Power
underfreq
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a036
Power phase
loss
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a037
Power phase
reverse
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a038
Liquid pipe
temp sensor
fault
Major
The alarm
is
generated.
1.
The liquid pipe
temperature sensor is
faulty.
2.
Cables to the liquid pipe
temperature sensor are
loose or damaged.
1.
Maintain or replace
the liquid pipe
temperature sensor.
2.
Check cables to the
liquid pipe
temperature sensor.
a042
Remote
shutdown
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
The remote shutdown
switch has
misoperations.
2.
The remote shutdown
switch is faulty, or cables
to the remote shutdown
switch are loose or
damaged.
1.
Check the status of the
remote dry contact.
2.
Check the shutdown
button and cables of
the remote dry contact.
a043
Floor water
overflow
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
Water exists on the floor.
2.
The water sensor is
faulty.
1.
Check and clean the
water.
2.
Maintain or replace
the water sensor.
a044
Smoke
detected
Critical
The alarm
is
generated,
and the
1.
Smoke is generated in
the equipment room.
2.
Cables to the smoke
sensor are loose or
1.
Exhaust smoke from
the equipment room
and reset the smoke
sensor.