NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
90
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
2.
Dirt or water exists
around the board, which
leads to a detection fault.
3.
The temperature and
humidity collection
board is faulty.
3.
Maintain or replace
the temperature and
humidity collection
board in the hot aisle.
a113
Hot aisle
1/2/3 T/H brd
comm fail
Major
The alarm
is
generated.
1.
DIP switches of the
temperature and
humidity collection
board are incorrectly set.
2.
Cables to the
temperature and
humidity collection
board are loose or
damaged.
3.
The temperature and
humidity collection
board is faulty.
1.
Set DIP switches by
referring to
3.8.6
Installing T/H
Sensors
.
2.
Check cables to the
temperature and
humidity collection
board.
3.
Maintain or replace
the temperature and
humidity collection
board in the hot aisle.
5.5 Troubleshooting
Certain circuits in the NetCol5000-A020 have lethal voltage. Only professional
technicians are allowed to perform maintenance.
Exercise caution during live-line troubleshooting.
If jumpers are used for troubleshooting, remove them after troubleshooting. Connected
jumpers may affect control functions and damage equipment.
5.5.1 The NetCol5000-A020 Generates Abnormal Voice
Symptom
The NetCol5000-A020 generates abnormal voice.
Possible Causes
Compressors, fans, or pipes are loose.
Procedure
Step 1
Check whether the compressor fastening bolts are loose.