Height of the U-shaped clamp H = Pipe diameter (with thermal insulation foam) – 5 mm.
The pipe support is not configured by default.
Cable Specifications
Table 3-7
lists specifications of power cables and cables to the host. The cables must be
protected by a protective tube when connecting the power cables and the external signal
cables.
Table 3-7
Cable specifications
Application
Scenario
Name
Technical
Specifications
Description Remarks
Power cable to
the indoor unit
Power cable
(optional)
Power cable-600 V/1000
V-ZA-RVV-4 mm
2
-32 A
L1/L2/L3/N/P
E (5-core)
Length
depending
on the site
survey
result
Power cable
terminal
(mandatory)
naked crimping
terminal-single cord end
terminal-4 mm
2
-20
A-inserted depth 10 mm
L1/L2/L3/N/P
E (cord end
terminal)
10 pcs
Cable to the
group control
networking and
host
Network
cable
(mandatory)
J73 of main control board
to RS-485 port of EMS, 8
pin
5 m
1 pcs
Voltage jumper (mandatory)
N/A
N/A
1 pcs
Water sensor (optional)
Power cable -5
m-22AWG-(2*T0.5
2
)-(2*
22UL1007)-(2*T0.5
2
)
N/A
1 pcs
Temperature and humidity
(T/H) sensor (optional)
Standard networking
cables, 6 pin
N/A
A
maximum
of six T/H
sensors
can be
configured
for a unit.
General circuit breaker
(unconfigured)
Rated working voltage:
400 V-Rated working
current: 32 A-
Interrupting capacity: 6
kA-Tripping
characteristics: C-3 pole
External
circuit
breaker
1 pcs
Note: For specifications of outdoor unit power cables and signal cables to the indoor and
outdoor units, see
NetCol500 Outdoor Unit User Manual
.