5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
118
Procedure
Step 1
Tap
Shutdown
on the main menu, switch off the main circuit breaker QF1 and the front end
circuit breaker.
Exercise cautions when performing operations on the equipment because the equipment is
under power.
Remove the rear door and the air filters when switch off the main circuit breaker QF1.
Step 2
Remove the front door, cables to the controller, and ground cables.
Step 3
Remove the R-shaped cable ties fixing the temperature sensor on the front door column using
a Phillips screwdriver, take down the supply air temperature sensor, and cut off the cable ties
fixing cables to the sensor.
Step 4
Disconnect the waterproof connectors from the sensor cables 50 cm below the sensor.
Step 5
Install the new sensor probe and fix it using R-shaped cable ties.
Step 6
Connect the waterproof connectors to sensor cables.
Step 7
Install the front door and properly connect signal and ground cables.
Step 8
Install the air filters and the rear door if no problem is found.
----End
5.6.9 Replacing an T/H Sensor
Prerequisites
The T/H sensor needs to be replaced.
A spare and functional T/H sensor is available.
Context
The rear door is opened for rear-access maintenance.
Procedure
Step 1
Tap
Shutdown
on the main menu, switch off the main circuit breaker QF1 and the front end
circuit breaker.