NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73
Item
Operations
Troubleshooting
Result
Check that the indoor fan
blades are intact.
Replace the fan by referring to
5.6.2 Replacing an Indoor Fan
.
Check that the indoor fans
do not generate abnormal
voice during operation.
Replace the fan by referring to
5.6.2 Replacing an Indoor Fan
.
Check that the screws on
the indoor fans are not
loose or distorted.
Retighten the screws.
Electric
heater
Check that the electric
heater and its switch are
fixed reliably.
Retighten the electric heater and its
switch.
Check that the electric
heater surfaces are not
eroded.
Replace the electric heater by
referring to
5.6.5 Electric Heater
.
Float
Check that the float
functions smoothly.
Replace the float by referring to
5.6.11 Replacing the Float
.
Air filters
Check that the filters are
not blocked.
Clean the air filters (water cleaning
is recommended).
Check that the filters are
not damaged or distorted.
Replace air filters by referring
to
5.6.1 Replacing Air Filters
.
Compressor
Check that the
compressor is fastened
properly.
Retighten the compressor screws.
Check that the refrigerant
oil is not on the valve.
Clean the refrigerant oil on the
valve.
Check that the sound of
the compressor is
properly.
Replace the compressor by
referring to
5.6.3 Replacing the
Compressor
Evaporator
Check that no foreign
matter exists on the
evaporator surface.
Clean the foreign matter.
Humidifier
Press the manual drainage
button of the humidifier
to "I" and check whether
the water drainpipe works
properly. Press the
manual drainage button of
the humidifier to "O" and
check whether the water
inlet works properly.
Drainage is abnormal
1.
Water outlet solenoid cannot
open, replace it.
2.
Drainpipe is blocked and
need to be cleaned.
Water inlet is abnormal
1.
Water inlet solenoid cannot
open, replace it.
2.
Water inlet pipe is blocked
and need to be cleaned.
Check that thermal
Replace the thermal insulation