Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
system
shuts down.
disconnected.
circuit C.
a088
Route D fuse
disconnect
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
A device on circuit D is
faulty.
2.
The fuse on circuit D is
loose, aged, or
disconnected.
1.
Maintain or replace
the faulty device on
circuit D.
2.
Replace the fuse on
circuit D.
a093
Return-air
humid high
Warning
The alarm
is
generated.
1.
The return air high
humidity alarm threshold
is inappropriate for the
working conditions.
2.
The humidity displayed
on the LCD is different
from the actual humidity.
1.
Adjust the return air
high humidity alarm
threshold.
2.
Calibrate or replace
the T/H sensor.
a094
Return-air
humid low
Warning
The alarm
is
generated.
1.
The return air low
humidity alarm threshold
is inappropriate for the
working conditions.
2.
The humidity displayed
on the LCD is different
from the actual humidity.
1.
Adjust the return air
low humidity alarm
threshold.
2.
Calibrate or replace
the T/H sensor.
a103
Indoor fan
power alarm
Major
The alarm
is
generated,
and the
compressor
shuts down.
1.
The power module is
faulty.
2.
Cables to the power
module are loose or
damaged.
1.
Maintain or replace
the power module.
2.
Check cables to the
power module.
a105
Indoor fan
failure
Critical
The alarm
is
generated,
and the
compressor
shuts down.
1.
Indoor fans are faulty.
2.
Cables to indoor fans are
loose or damaged.
1.
Maintain or replace
the indoor fans.
2.
Check cables to indoor
fans.
a107
Mains outage
Warning
The alarm
is
generated,
and heating
and
humidificati
on
operations
are
prohibited.
1.
Power supply circuits are
disconnected.
2.
The dry contact is faulty.
1.
Check the power
supply circuits.
2.
Check the dry contact.
a108
Cold aisle
1/2/3 temp
invalid
Major
The alarm
is
generated.
1.
The T/H sensor in the
cold aisle fails to
communicate with the
1.
Handle the Cold aisle
1/2/3 tem invalid
alarm.