NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
89
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
main control board.
2.
Dirt or water exists
around the board, which
leads to a detection fault.
3.
The temperature and
humidity collection
board is faulty.
2.
Clean the temperature
and humidity
collection board in the
cold aisle.
3.
Maintain or replace
the temperature and
humidity collection
board in the cold aisle.
a109
Cold aisle
1/2/3 humid
invalid
Major
The alarm
is
generated.
1.
The temperature and
humidity collection
board in the cold aisle
fails to communicate
with the main control
board.
2.
Dirt or water exists
around the board, which
leads to a detection fault.
3.
The temperature and
humidity collection
board is faulty.
1.
Handle the Cold aisle
1/2/3 humid invalid
alarm.
2.
Clean the temperature
and humidity
collection board in the
cold aisle.
3.
Maintain or replace
the temperature and
humidity collection
board in the cold aisle.
a110
Cold aisle
1/2/3 T/H brd
comm fail
Major
The alarm
is
generated.
1.
DIP switches of the T/H
sensor are incorrectly set.
2.
Cables to the
temperature and
humidity collection
board are loose or
damaged.
3.
The T/H sensor is faulty.
1.
Set DIP switches by
referring to
3.8.6
Installing T/H
Sensors
.
2.
Check the temperature
and humidity sensor
and cables.
3.
Maintain or replace
the temperature and
humidity collection
board in the cold aisle.
a111
Hot aisle
1/2/3 temp
invalid
Major
The alarm
is
generated.
1.
The temperature and
humidity collection
board in the hot aisle
fails to communicate
with the main control
board.
2.
Dirt or water exists
around the board, which
leads to a detection fault.
3.
The temperature and
humidity collection
board is faulty.
1.
Handle the Hot aisle
temp invalid alarm.
2.
Clean the temperature
and humidity
collection board in the
hot aisle.
3.
Maintain or replace
the temperature and
humidity collection
board in the hot aisle.
a112
Hot aisle
1/2/3 humid
invalid
Major
The alarm
is
generated.
1.
The temperature and
humidity collection
board in the hot aisle
fails to communicate
with the main control
board.
1.
Handle the Hot aisle
humid invalid alarm.
2.
Clean the temperature
and humidity
collection board in the
hot aisle.