NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
75
Item
Operations
Troubleshooting
Result
and float
condensate water pan and
float.
matter from the floats.
Table 5-3
Semiannual maintenance items
Item
Operations
Troubleshooting
Result
Components
in the
electric
control box
(removing
the
electrical
control box
to maintain
according to
5.6.7
Replacing
Components
in the
Electric
Control Box
Check that all circuit
breakers and fuses are
working properly.
Replace the abnormal circuit
breaker and fuse.
Check and fasten all
circuit connections.
Fasten all circuit connections
Check that each input and
output connector between
the main control board
and the display panel and
between the main control
board and the T/H sensor
have proper contact.
Reconnect the abnormal terminals.
Check that each input and
output connector between
the main control board
and contactors, solenoid
valves, high-/low-pressure
switches, electric heater
temperature switch have
proper contact.
Reconnect the abnormal terminals.
Check that various
electric components,
control components, and
the surge protection and
voltage test board are
dirty.
Use a brush or compressed dry air
to clean various electric
components, control components,
and the surge protection and
voltage test board.
Check that the main
control board, LCD, T/H
sensor, and surge
protection and voltage test
board are not aging on the
surface.
Replace the abnormal boards.
Perform static tests to
check whether each
contactor has a flexible
pickup.
Replace the abnormal parts.
Check that the
transformer is not intact
and the output voltage is
Replace the transformer