NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
2 Product Description
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
14
Item
Specifications
Filter level
G3
Dimensions (H x W x D)
2000 mm x 300 mm x 1000 mm
Net weight/Gross weight
230 kg/275 kg
If the equipment room does not have requirements for humidity, air conditioners that do
not have humidification function or have partial humidification function are
recommended.
When the total load of servers is less than 30% load of a single air conditioner, the
humidity might be relatively high. In this case, contact Huawei technical support.
Table 2-6
Optional parameters
Item
Specifications
NetCol5000-A
020
HM13N10020
E0
NetCol5000-A
020
HM13N1E120
E0
NetCol5000-A
020
HQ13N10020
E0
NetCol5000-A
020
HQ13N1E120
E0
Maximum
current
16.5 A
23 A
16.5 A
23 A
Input power
380–415 V AC
50 Hz 3W + N
+ PE
380–415 V AC
50 Hz 3W + N
+ PE
380 V AC 60
Hz 3W + N +
PE
380 V AC 60
Hz 3W + N +
PE
Voltage
tolerance
a
Rated
voltage±10%
Rated
voltage±10%
Rated
voltage±10%
Rated
voltage±10%
Frequency
tolerance
Rated
frequency±3 Hz
Rated
frequency±3 Hz
Rated
frequency±3 Hz
Rated
frequency±3 Hz
Heating
None
Configured
None
Configured
Humidification
None
Configured
None
Configured
a: Recommended to add the voltage regulator in the front end if the power exceeds this
range. Otherwise, air conditioner will generate frequency alarms and cannot run.