NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
55
Switch
Default Value
Description
8
ON
Remaining in ON.
----End
3.8.6 Installing T/H Sensors
To install the T/H sensors, you need to connect cables to the sensors and set DIP switches for
the sensor.
Context
If more than one T/H sensor is connected to an air conditioner, the air conditioner must
differentiate various T/H sensors based on DIP switch settings on the sensors that change their
communications addresses.
Figure 3-34
shows an T/H sensor.
Figure 3-34
T/H sensor
Fix cables to the T/H sensor using cable ties.
The T/H sensor is used to detect hot/cold aisle temperature. Determine the installation
position of the T/H sensor based on the site situation. You are recommended to deploy the
T/H sensor at a place where a heat point is most likely to appear in the hot or lack in cold
aisle.
Procedure
Step 1
Connect the RS485_OUT of the upstream sensor to RS485_IN of the downstream sensor.
Figure 3-35
shows cable connection of T/H sensors.