5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
93
Step 2
Check whether the compressor starts and stops continuously or the compressors has a dull
noise.
If the compressor starts and stops continuously, deal with it by referring to
Comp HP
switch
, and then check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 3
.
If the compressors has a dull noise, go to
Step 3
.
If the compressor does not start and stop continuously, go to
Step 3
.
Step 3
Contact Huawei technical support.
----End
5.5.4 An Indoor Fan Fails to Start
Symptom
An indoor fan fails to start.
Possible Causes
Indoor fan fault alarms exist.
An indoor fan does not need to start.
Either the general circuit breaker or the indoor fan circuit breaker is not switched on.
Power to the indoor fan is abnormal.
Procedure
Step 1
Check whether there are indoor fan fault alarms.
If yes, deal with it by referring to
5.4 Alarm Reference
and then check whether the fault
is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 2
.
If yes, go to
Step 2
.
Step 2
Check for any startup requirement for fans on the LCD.
Tap
Running
>
Status
to check the fan control, if it is 0%, meaning the indoor fans do
not need to start, it is not faulty, troubleshooting is complete.
If the fan control is greater than 0%, meaning the indoor fans need to start, go to
Step 3
.
Step 3
Check whether the circuit breakers are switched on.
If no, switch on the circuits and then check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 4
.
If no, go to
Step 4
.
Step 4
Check whether the indoor fan power supply is normal.