Procedure
Step 1
Tap
Shutdown
on the main menu, switch off the main circuit breaker QF1 and the front end
circuit breaker.
Exercise cautions when performing operations on the equipment because the equipment is
under power.
Remove the rear door and the air filters when switch off the main circuit breaker QF1.
Step 2
Push down the buckle button on the power module, as shown in 1 of
Figure 5-16
.
Figure 5-16
Removing the power module
Step 3
Pull out the buckle, as shown in 2 of
Figure 5-16
, and then pull out the power module from
plug-in frame.
Step 4
Push the spare power module to the plug-in frame and push upward the buckle button to lock
the power module.
Step 5
Install the air filters and rear door if no problem is found.
----End