Exercise cautions when performing operations on the equipment because the equipment is
under power.
Remove the rear door and the air filters when switch off the main circuit breaker QF1.
Step 2
Remove cables and connectors to side and bottom of the electrical control box.
Step 3
Remove two front bolts fixing the electrical control box (as shown in 1 of
Figure 5-12
), hold
the handle, lift the electrical control box, pull out the electrical control box along the guide
rails (as shown in 2 of
Figure 5-12
), and place it on the ground in a horizontal manner.
Figure 5-12
Dismantling the electric control box
Step 4
Remove screws on the cover of the electrical control box using the Phillips screwdriver, open
the electrical control box, and replace faulty components in the electrical control box.
This section uses replacing the main control board in the electrical control box as an example.
Step 5
After replacing the main control board, install the cover back to the electric control box.
Step 6
Place the electric control box back to the original place, and secure the electric control box.
Step 7
Connect cables and connectors to the electrical control box.