NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
54
Figure 3-33
Network diagram for teamwork communication and monitoring
The number of air conditioners in the preceding figure is less than or equal to 32.
Com1 port is J73UP port, Com2 port is J73DOWM port.
Step 2
Set DIP switches on the main control board, as shown in
Table 3-11
.
Set the position of switch 7 onsite based on the application scenarios and ensure that other
DIP switches are in the default position, as shown in
Table 3-11
.
Table 3-11
Operation of the switches on the main control board
Switch
Default Value
Description
1
OFF
Remaining in OFF.
2
OFF
Remaining in OFF.
3
ON
Remaining in ON.
4
ON
Remaining in ON.
5
OFF
Remaining in OFF.
6
ON
Remaining in ON.
7
OFF
When teamwork mode is not deployed, remain in OFF.
When teamwork mode is deployed, toggle switches on
the main control boards of the first and last units (such
as air conditioner 1 and air conditioner n shown in
Figure 3-33
) to ON and other remains in OFF.