5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
108
Figure 5-7
Replacing the humidifier cylinder
Step 4
Remove cables to the electrode and high water level sensor above the humidifier cylinder.
Step 5
Untie the bind strap on the humidifier cylinder and remove the humidifier cylinder, as shown
in 2 of
Figure 5-7
.
Step 6
Install a new humidifier cylinder by reversing operations in
Step 3
to
Step 5
.
Step 7
Fasten the tie on the humidifier cylinder.
Step 8
Power on the humidifier, choose
Maint
>
Diagnosis mode
on the main menu, and enter
100%. The water is injected to the humidifier. Check whether the humidifier works properly.
If yes, exit the diagnosis mode.
Step 9
Drain the water from the humidifier cylinder by following the instructions provided in
Step 1
.
Step 10
Install the air filters and rear door if no problem is found.
----End
Follow-up Procedure
Choose
Maint
>
Performance Maint
on the main menu, and clear the accumulated running
time of the humidifier.