Figure 3-32
DIP switch position
(1) Teamwork communications ports J73UP and
J73DOWN
(2) DIP switches on the main
control board
(3) J127 FE port (reserved)
Procedure
Step 1
Connect the networked air conditioner, as shown in
Figure 3-33
.
When only teamwork networking is deployed, reserve J73UP on the first unit, connect
J73DOWN of the unit to J73UP of the second unit, J73DOWN of the second unit to
J73UP of the third unit. In this way, connect all units involved in teamwork networking,
as shown by
CAN bus
in
Figure 3-33
.
When both teamwork networking and RS485 monitoring are deployed, connect J73UP
of the first unit or J73DOWN of the last unit to the host over RS485, as shown by
RS-485 bus
in
Figure 3-33
.