NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
82
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
exceed
runtime
is
generated.
the air filters exceeds the
alarm threshold.
air filters. For details
about how to replace the
air filters, see
5.6.1
Replacing Air Filters
.
Clear the accumulated
runtime.
a027
Power loss
Warning
The alarm
is
generated.
The NetCol5000-A020 is
disconnected.
Check power cable to the
NetCol5000-A020.
a028
Power phase
A overvolt
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a029
Power phase
B overvolt
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a030
Power phase
C overvolt
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a031
Power phase
A undervolt
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a032
Power phase
B undervolt
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a033
Power phase
C undervolt
Major
The alarm
is
generated,
and the
system
shuts down.
1.
The power grid is
unstable.
2.
The surge protection and
voltage test board is
faulty.
1.
Check the power grid.
2.
Replace the surge
protection and voltage
test board.
a034
Power
Major
The alarm
1.
The power grid is
1.
Check the power grid.