NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
78
5.4 Alarm Reference
Table 5-4
describes alarms for the air cooled in-row precision air conditioner
NetCol5000-A020.
Table 5-4
Alarm reference
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
a001
Return-air 1
temp invalid
Major
The alarm
is
generated.
1.
Cables to the
temperature sensor at
return air vent 1 are
loose or damaged.
2.
The return air
temperature sensor is
faulty.
1.
Check cables to the
temperature sensor at
return air vent 1.
2.
Maintain or replace
the temperature sensor
at return air vent 1.
Return-air 2
temp invalid
Major
The alarm
is
generated.
1.
The T/H sensor at return
air vent 2 fails to
communicate with the
main control board.
2.
Dirt or water exists
around the T/H sensor,
which leads to a
detection fault.
3.
The T/H sensor at return
air vent 2 is faulty.
1.
Handle the Return air
2 temp invalid alarm.
2.
Clean the T/H sensor
at return air vent 2.
3.
Maintain or replace
the T/H sensor at
return air vent 2.
a002
Return-air HT Critical
The alarm
is
generated.
1.
The return air high
temperature alarm
threshold is
inappropriate for the
working conditions.
2.
The temperature
displayed on the LCD is
different from the actual
temperature.
3.
The refrigeration
capacity of the
NetCol5000-A020 is
insufficient or the heat
load is high.
4.
The ambient temperature
is higher than the upper
alarm threshold.
1.
Adjust the high
temperature alarm
threshold.
2.
Calibrate or replace
the T/H sensor.
3.
Add more
NetCol5000-A020
units.
4.
Check the ambient
temperature.
a003
Return-air LT
Warning
The alarm
is
generated.
1.
The return air low
temperature alarm
threshold is
inappropriate for the
working conditions.
2.
The temperature
displayed on the LCD is
different from the actual
1.
Adjust the return air
low temperature alarm
threshold.
2.
Calibrate or replace
the T/H sensor.
3.
Check the ambient
temperature.