NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
81
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
generated.
shutdown period for the
compressor are
inappropriately set.
2.
This alarm is affected by
other alarms.
3.
The T/H sensor is faulty.
4.
The load in the
equipment room is low.
shortest shutdown
period for the
compressor.
2.
Clear other alarms.
3.
Maintain or replace
the T/H sensor.
4.
Increase the
temperature precision.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a015
Comp exceed
runtime
Warning
The alarm
is
generated.
The accumulated runtime of
the compressor exceeds the
alarm threshold.
Maintain or replace the
compressor. For details
about how to replace a
compressor, see
5.6.3
Replacing the
Compressor
. Clear the
accumulated runtime.
a018
Indoor fan
1/2/3/4/5/6/7/
8 exceed
runtime
Warning
The alarm
is
generated.
The accumulated runtime of
the fan exceeds the alarm
threshold.
Maintain or replace the
indoor fans. For details,
see
5.6.2 Replacing an
Indoor Fan
. Clear the
accumulated runtime.
a022
Humidifier
exceed
runtime
Warning
The alarm
is
generated.
The humidifier accumulated
runtime exceeds the alarm
threshold.
Maintain or replace the
humidifier. For details
about how to replace a
humidifier, see
5.6.4
Replacing the Humidifier
Cylinder
. Clear the
accumulated runtime.
a023
Elec heater
HT
Major
The alarm
is
generated,
and the
electric
heater shuts
down
forcibly.
1.
Cables to the
temperature switch of the
electric heater are loose
or damaged.
2.
The temperature switch
is faulty.
3.
The manual reset
temperature switch is not
reset.
1.
Check cables to the
temperature switch of
the electric heater.
2.
Maintain or replace
the temperature
switch.
3.
Reset the manual
temperature reset
switch.
a024
Elec heater
exceed
runtime
Warning
The alarm
is
generated.
The accumulated runtime of
the electric heater exceeds
the alarm threshold.
Maintain or replace the
electric heater. For details
about how to replace the
electric heater, see
5.6.5
Electric Heater
. Clear the
accumulated runtime.
a026
Air filter
Warning
The alarm
The accumulated runtime of
Maintain or replace the