B Laying out the Cooling System
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
125
B
Laying out the Cooling System
A complete cooling system is composed of the indoor NetCol5000-A020 and outdoor
NetCol500.
Figure B-1
shows the layout of various components of the cooling system.
Figure B-1
Laying out the Cooling System
(1) Compressor
(2) Check
valve
(3) Oil trap
(4) Outdoor unit
(5) Inverted trap
(6) Filter drier
(7) Sight
glass
(8) Liquid solenoid
valve
(9) Thermostatic expansion
valve
(10)
Evaporator
(11) Indoor
fan
(12) Hot gas bypass
valve
Figure B-1
the pipelines in solid line are installed by Huawei before delivery.
Figure B-1
the pipelines in dashed line are to be routed onsite by technical personnel.
Huawei does not provide the inverted traps (component 5) and oil traps (component 3). However, to
ensure the normal operating and easy maintenance of the cooling system, it is recommended that you
use these two components.