NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
20
Figure 3-2
Water inlet pipe and connector for a humidifier
(1) Inner thread connector: BSPP,
3/4 inch
(2) Connector for rigid pipes: BSPT, 3/4 inch, outer
thread connector
(3) Rigid pipe: PP-R or C-PVC
(4) Pagoda connector: BSPT, 3/4 inch, outer thread
connector
(5) Hose clamp
(6) Hose: for example, EPDM
Part 1 (in the dot-line box) is a port on the equipment. Part 5 (hose clamp) is mandatory. Other parts
need to be configured.
Materials Required for Drainpipes
The drainpipe (for a humidifier) must withstand high temperature (higher than 100°C).
Otherwise, the drainpipe may be deformed due to high temperature.
Two drainpipe connection modes are provided:
Rigid pipe: Fix one end of a hose to the inlet of the equipment using a hose clamp and
the other end of the hose to a connector to connect to a rigid pipe with outer threads, as
shown in
of
Figure 3-3
.
Hose: Fix the hose to the inlet of the equipment as shown in
of
Figure 3-3
.
Determine connection methods based on materials prepared onsite.