NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
119
Exercise cautions when performing operations on the equipment because the equipment is
under power.
Remove the rear door and the air filters when switch off the main circuit breaker QF1.
Step 2
Remove terminals connecting to RS485_IN and RS485_OUT.
Step 3
Pull out the T/H sensor, as shown in
Figure 5-15
.
Figure 5-15
Replacing an T/H sensor
Step 4
Install a new ambient temperature and humidity sensor and connect terminals to RS485_IN
and RS485_OUT.
Step 5
Install the air filters and rear door if no problem is found.
----End
5.6.10 Replacing the Power Module
Prerequisites
The power module needs to be replaced.
A spare and functional power module is available.
Context
The rear door is opened for rear-access maintenance.