background image

255040-YTG-A-0506

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE

AIR CONDITIONERS

D(CE, CG) 036, 048, 060 & 072

3, 4, 5 & 6  NOMINAL TONS

10.0 SEER (3, 4, & 5 Ton), 9.0 EER (6 Ton)

®  

TECHNICAL GUIDE

DESCRIPTION

YORK Sunline 2000™ units are convertible single package 
air conditioners with a common cabinet and a common roof 
curb for the 3, 4, 5 and 6 ton sizes. The units were designed 
for light commercial and commercial applications. They can 
easily be installed on a roof curb, slab, roof jack or frame.

All units include:

Powder Paint finish that meets ASTM-B-117 1000 hour 
salt spray standards

Permanently lubricated motors

Bottom or side air discharge configuration capability 
(field convertible)

Manufactured under the quality standards of ISO9001

Copper tube/aluminum fin coils

Easy access to all components

Rigging holes in base rails for lifting

Fork lift slots on three sides

Single point power connection

Complete factory package - tested, charged and wired

CSA agency listing on all units

WARRANTY

Factory Limited Parts Warranty

One-year parts warranty

A Five-year parts warranty on the compressor and
electric heat elements.

Ten-year parts warranty on the gas-fired heat
exchangers.

Содержание 36

Страница 1: ...oof curb slab roof jack or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration cap...

Страница 2: ...COOLING UNIT POWER CIRCUIT 460 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM 36 19 COOLING UNIT POWER CIRCUIT 575 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM 37 20 COOLING UNIT POWER CIRCUIT 575 3 60 BELT DRIVE I...

Страница 3: ...072 6 Ton 3 0 6 2 5 NOMINAL COOLING CAPACITY FACTORY INSTALLED HEAT A Cooling Only D 8 C G 4 N PRODUCT GENERATION 3 3rd Generation 8 8th Generation PRODUCT CATEGORY D Single Package Air Conditioner A...

Страница 4: ...applicable and the temperature limit switch on gas heat units The unit control board will alarm on ignition failures compressor lockouts and repeated limit switch trips Nuisance Trip Protection To pr...

Страница 5: ...ng return motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the...

Страница 6: ...er the outdoor air intake dampers are opened for free cooling the exhaust fan will be energized to prevent the condi tioned space from being over pressurized during econo mizer operation The power exh...

Страница 7: ...of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At a distance of 10 feet from...

Страница 8: ...0 34 33 29 25 21 17 13 62 33 3 7 33 33 33 29 25 21 17 31 4 0 31 31 31 27 23 19 15 57 34 3 6 34 34 34 30 26 22 18 32 4 0 32 32 32 28 24 20 16 72 39 3 7 27 24 20 17 14 37 4 1 26 23 20 16 13 67 36 3 6 34...

Страница 9: ...45 42 37 32 27 22 17 62 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 26 21 57 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 25 20 72 53 5 0 36 32 28 23 19 51 5 5 35 31 26 22 17 67 46 4 9 44...

Страница 10: ...5 50 47 42 36 30 24 18 62 48 5 8 48 48 48 42 37 31 25 44 6 4 44 44 44 38 32 26 20 57 46 5 8 46 46 46 40 35 29 23 42 6 4 42 42 42 36 31 25 19 72 60 6 0 42 37 32 26 21 57 6 6 41 36 30 25 20 67 54 5 8 52...

Страница 11: ...9 66 61 54 47 40 32 25 62 64 7 0 64 64 64 56 49 42 35 58 7 8 58 58 58 51 43 36 29 57 64 7 0 64 64 64 56 49 42 34 58 7 7 58 58 58 50 43 36 29 72 75 7 1 56 49 43 36 29 76 8 0 55 48 41 34 27 67 70 7 1 68...

Страница 12: ...0 580 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 1600 1500 1400 1055 875 1300 1036 780 1066 850 1200 1011 735 1047 765 1075 800 1100 987 690 1028 720 1060 750 1084 775...

Страница 13: ...WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003...

Страница 14: ...5 830 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 1133...

Страница 15: ...PM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 3000 2800 1245 2190 2600 1193 1920 1222 1990 1250 2060 2400 1142 1675 1173 1730 1205 1800 1234 1885 2200 1090 1380 1124 1450 1155 1550 1...

Страница 16: ...24 800 1644 770 1531 710 6 1 HI 2101 1260 2000 1205 1914 1155 1830 1110 5 1 0 60 0 20 0 30 0 40 0 50 UNIT TONNAGE MOTOR SPEED UNIT TONNAGE MOTOR SPEED 3 1 4 1 5 1 AVAILABLE EXTERNAL STATIC PRESSURE IW...

Страница 17: ...h the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer oper...

Страница 18: ...45107462 6 8 8 2 13 15 2CE045110462 10 1 12 1 17 9 20 2CE045115462 13 6 16 4 23 2 25 2CE045120462 19 5 23 5 32 1 35 575 3 60 5 0 36 0 0 8 2 2 None 8 7 15 2CE04511058 10 6 10 2 14 9 15 2CE04511558 15 9...

Страница 19: ...15 3 22 4 25 2CE04512058 21 2 20 4 28 8 30 2CE04513058 30 4 29 3 39 9 40 D CE CG 072 6 0 208 3 60 18 9 146 0 1 3 6 8 None 31 7 40 2CE045105252 4 11 1 31 7 40 2CE045107252 5 6 15 5 31 7 40 2CE04511025...

Страница 20: ...07462 6 8 8 2 13 5 15 2CE045110462 10 1 12 1 18 4 20 2CE045115462 13 6 16 4 23 7 25 2CE045120462 19 5 23 5 32 6 35 575 3 60 5 0 36 0 0 8 2 0 None 8 9 15 2CE04511058 10 6 10 2 15 2 20 2CE04511558 15 9...

Страница 21: ...8 15 9 15 3 21 6 25 2CE04512058 21 2 20 4 28 30 2CE04513058 30 4 29 3 39 1 40 D CE CG 072 6 0 208 3 60 18 9 146 0 1 3 5 0 None 29 9 40 2CE045105252 4 11 1 29 9 40 2CE045107252 5 6 15 5 29 9 40 2CE0451...

Страница 22: ...400 3400 3400 CONDENSER COILS Rows Deep 1 1 1 2 Fins Per Inch 16 16 22 16 Face Area Sq Ft 17 1 17 1 17 1 16 7 COMPRESSOR Qty Per Unit Scroll Type 1 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2...

Страница 23: ...S WHEN THE THERMOSTAT SWITCHES TO THE SET BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANS...

Страница 24: ...255040 YTG A 0506 24 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 3 6 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 6 TON COOLING GAS HEAT FRONT VIEW...

Страница 25: ...255040 YTG A 0506 Unitary Products Group 25 FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD DETAIL A FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B...

Страница 26: ...RY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS D...

Страница 27: ...255040 YTG A 0506 Unitary Products Group 27 FIGURE 9 TYPICAL APPLICATIONS...

Страница 28: ...CG036N040 605 134 132 168 171 90 89 88 112 113 114 DCG036N079 625 139 136 173 177 93 92 91 115 117 118 DCE048 Cooling Electric 615 137 134 171 174 91 90 89 113 115 116 DCG048N060 665 148 145 184 188 9...

Страница 29: ...SIC UNIT DCE Cooling Only 565 615 640 720 DCG Gas Electric N040 605 N060 665 N079 625 700 780 N099 685 710 790 OPTIONS OR ACCY Economizer 50 Motorized Damper 26 Electric Heater 5 7 kW 18 10 15 kW 23 2...

Страница 30: ...255040 YTG A 0506 30 Unitary Products Group FIGURE 12 COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 208 230V AND 460V DIAGRAM...

Страница 31: ...255040 YTG A 0506 Unitary Products Group 31 FIGURE 13 COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 575 VOLT DIAGRAM...

Страница 32: ...255040 YTG A 0506 32 Unitary Products Group FIGURE 14 COOLING UNIT WITH ELECTRIC HEAT CONTROL CIRCUIT 208 230V 460V AND 575V DIAGRAM...

Страница 33: ...255040 YTG A 0506 Unitary Products Group 33 FIGURE 15 COOLING UNIT POWER CIRCUIT 208 230 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Страница 34: ...255040 YTG A 0506 34 Unitary Products Group FIGURE 16 COOLING UNIT POWER CIRCUIT 208 230 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Страница 35: ...255040 YTG A 0506 Unitary Products Group 35 FIGURE 17 COOLING UNIT POWER CIRCUIT 460 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Страница 36: ...255040 YTG A 0506 36 Unitary Products Group FIGURE 18 COOLING UNIT POWER CIRCUIT 460 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Страница 37: ...255040 YTG A 0506 Unitary Products Group 37 FIGURE 19 COOLING UNIT POWER CIRCUIT 575 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Страница 38: ...255040 YTG A 0506 38 Unitary Products Group FIGURE 20 COOLING UNIT POWER CIRCUIT 575 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Страница 39: ...ent All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be CSA listed classified to ANSI...

Страница 40: ...gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type constructed of T1 40 aluminized steel for corrosion resistance...

Страница 41: ...unit Water eliminator fil ters shall be provided Simultaneous economizer com pressor operation is also possible Dampers shall fully close on power loss OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF...

Страница 42: ...255040 YTG A 0506 42 Unitary Products Group...

Страница 43: ...255040 YTG A 0506 Unitary Products Group 43...

Страница 44: ...bject to change without notice Printed in U S A 255040 YTG A 0506 Copyright 2006 by Unitary Products All rights reserved Supersedes 530 18 TG1Y 500 Unitary 5005 Norman Products York OK Group Drive 730...

Отзывы: