ROOFTOP  UNITS 

48-50 UH-UA 

Accessory: Room-Mate  Comfort Controller 

 
 

 

INSTALLATION INSTRUCTIONS 

 

Package  Usage and  Contents 

 

Room-Mate Comfort Controller Package consists of the following components: 

 

•  (1) Room-Mate Comfort Controller (Figure–1) 
•  (2) 6-32" x 1" round head machine screws 

 

 

 

IMPORTANT: 

 

All installation operations must be carried out by technicians who have been trained on Carrier products, 
regarding all Carrier quality and safety standards. 

 

 

IMPORTANT: 

 

Read this instruction completely before attempting to install. 

 

 

WARNING: 

 

Remove power before wiring! Never connect or  disconnect wiring with power applied. Do  not  allow 
live wires to touch the controller’s circuit board. 

 

 

CAUTION: 

 

• 

Do not run the Room-Mate Comfort Controller wiring in any conduit with line powered wiring. 

 

• 

Room-Mate Comfort Controller is powered by 24Vac, the 24Vac power and ground wires should be 
run in a separate cable from signal wires. Separate the power cable from the signal cable by at least 
15cm (6 inches) along the entire wiring run. 

 

• 

Failure to wire devices with the correct polarity using a shared transformer may result in damage to 
any device powered by the shared transformer. 

 

• 

The Room-Mate Comfort Controller measures building interior temperature and should be located on 
an interior building wall. The controller can be mounted directly on the wall surface if acceptable by 
local codes. 

 

• 

Do  not  mount  the  controller  in  drafty  locations  such  as  near  air  conditioning or  heating  ducts,  over 
heat sources such as baseboard heaters, radiators, or directly above wall mounted lighting dimmers. 
Do  not  mount  the  controller  near  a  window  that  may  be  opened,  or  near  a  wall  corner  or  door. 
Controllers mounted in these areas will have inaccurate and erratic sensor readings. 

 

• 

Mount the controller approximately 150cm (5  ft)  from the floor, in  an  area representing the average 
temperature  in  the  space.  Allow  at  least  120cm  (4  ft)  between  the  controller  and  any  corner  and 
mount the controller at least 60cm (2 ft) from an open doorway. 

 

• 

Clean controller with damp cloth only. Do not use solvents. 

 

 

 

Содержание 48-50 UH-UA

Страница 1: ...gnal wires Separate the power cable from the signal cable by at least 15cm 6 inches along the entire wiring run Failure to wire devices with the correct polarity using a shared transformer may result in damage to any device powered by the shared transformer The Room Mate Comfort Controller measures building interior temperature and should be located on an interior building wall The controller can ...

Страница 2: ... wiring with power applied Do not allow live wires to touch the controller s circuit board 1 Carefully separate the cover from the base by pulling the cover and base apart towards the bottom of the device The hex screw may need to be turned in to release the cover 2 Route the wires through the access hole in the center of the base and screw them into the terminal blocks ...

Страница 3: ...ll controller installations For additional wiring instructions see diagram 5726419 and 5726421 4 Attach the base directly to drywall or to a standard 2 x 4 junction box using the hardware provided 5 After wiring attach the cover to the base and turn out the hex screw until the cover cannot be removed Figure 1 Room Mate Comfort Controller ...

Страница 4: ...ow The number of wires needed depends on the application Using the provided wire nuts attach the required wires to the proper connector leads based on the connector pins used by your application CONNECTOR PIN CONNECTOR LEAD COLORS 1 BLUE 2 BLACK 3 RED 4 GREEN 5 YELLOW 6 WHITE FRONT VIEW REA R VIEW WIRE NUMBER WIRE COLOR PIN1 NOTE Wire number corresponds to connector pin number 1 BLU 2 BLK 3 RED 4 ...