6.3.3
Quick Setup "Communication"
To establish cyclic data transfer, various arrangements between the PROFIBUS master (Class 1) and
the measuring device (slave) are required which have to be taken into consideration when
configuring various functions. These functions can be configured quickly and easily by means of the
"Communication" Quick Setup. The following table explains the parameter configuration options in
more detail.
a0002600-en
Fig. 86:
Quick Setup communication
+
+
E
+
E
B
Quick Setup
Quick Setup
6101
6140
6141
1006
Esc
E
+
-
XXX.XXX.XX
HOME-POSITION
Fieldbus Address
Selection
GSD
Unit To Bus
Setup
Communication
Quick Setup "Communication"
HOME position
→
F
→
MEASURED VARIABLE (A)
MEASURED VARIABLE
→
O
→
QUICK SETUP (B)
QUICK SETUP
→
N
→
QUICK SETUP COMMUNICATION (1006)
Function No.
Function name
Setting to be selected (
P
)
(to next function with
F
)
1006
QUICK SETUP
COMMUNICATION
YES
→
After
F
is pressed by way of confirmation, the Quick
Setup menu calls up all the subsequent functions in succession.
6101
FIELDBUS ADDRESS
Enter the device address (permitted address range: 1 to 126)
Factory setting:
126
6140
SELECTION GSD
Select the operating mode (GSD file) which should be used for
cyclic communication with the PROFIBUS master.
Options:
MANUFACT. SPEC.
→
The measuring device is operated in the
manufacturer-specific mode.
PROFILE-GSD
→
The measuring device is operated in the
PROFIBUS Profile mode.
Factory setting:
MANUFACT. SPEC.
!
Note!
For PROFIBUS network configuration, make sure that the right
device master file (GSD file) of the measuring device is used for
the selected operating mode