Installation
Proline Prosonic Flow 93 PROFIBUS DP/PA
22
Hauser
3.6.2
Determining installation distances via FieldCare
FieldCare is Hauser’s FDT-based plant asset management tool and allows the configuration
and diagnosis of intelligent field devices. The Proline flowmeters are accessed via a service interface
or via the service interface FXA193.
FieldCare and the FXA193 service interface can be ordered as accessories
Perform the following steps to determine the installation distances:
1.
Mount the wall-mount housing
2.
Connecting the power supply
3.
Connecting the PC to the plant asset management tool
4.
Switch on the measuring device.
5.
Read off the installation distances via FieldCare.
Installing the wall-mount transmitter housing
There are various ways of installing the wall-mount housing:
• Direct wall mounting
• Panel mounting (with separate mounting kit, accessories
• Pipe mounting (with separate mounting kit, accessories
"
Caution!
• Make sure that the permitted operating temperature range (-20 to +60 °C / –4 to +140 °F) is not
exceeded at the mounting location. Install the device in a shady location. Avoid direct sunlight.
• Always install the wall-mount housing in such a way that the cable entries are pointing down.
Direct wall mounting
1.
2.
Remove the cover of the connection compartment (a).
3.
Push the two securing screws (b) through the appropriate bores (c) in the housing.
– Securing screws (M6): max. Ø 6.5 mm (0.26")
– Screw head: max. Ø 10.5 mm (0.41")
4.
Secure the transmitter housing to the wall as indicated.
5.
Screw the cover of the connection compartment (a) firmly onto the housing.
A0001130
Fig. 14:
Direct wall mounting
a
b
c
c
90 (3.54)
35 (1.38)
192 (7.56)
81.5
(3.2)
mm (inch)