Installation
Proline Prosonic Flow 93 PROFIBUS DP/PA
20
Hauser
Running the "Sensor Installation" Quick Setup menu
!
Note!
• If you are not familiar with the operation of the device
75.
• The following section only describes the steps necessary for clamp-on and insertion type of
mounting within the "Sensor Installation" Quick Setup.
Running the Quick Setup for clamp-on type of mounting
1.
Enter or select installation-specific values or the values specified here.
2.
Read off the installation distances necessary for mounting.
Subsequent procedure
The sensors can be installed once the installation distances have been determined:
• Prosonic Flow P (DN 15 to 65 / ½ to 2½")
• Prosonic Flow P (DN 50 to 4000 / 2 to 160")
• Prosonic Flow W
Home position
→
Quick Setup
→
Setup sensor
↓
Language
QS sensor units
CH1
→
Channel
Clamp-on
→
Measurement
Sensor type
1 or 2
→
Sensor configuration
=
Number of traverses
Pipe standard
Nominal diameter
Pipe material
Sound velocity pipe
Pipe diameter
Circumference
Wall thickness
Liquid
Installation
distances for
measurement via
one traverse:
Installation
distances for
measurement via
two traverses:
Temperature
Sound velocity liquid
Position sensor
→
–
Wire length
→
–
Sensor distance
→
No
→
Other measurement?
No
→
Other channel?
↓
Setup sensor