Proline Prosonic Flow 93 PROFIBUS DP/PA
Installation
Hauser
17
3.6
Determining values for installation distances
3.6.1
Determining installation distances via local operation
Perform the following steps to determine the installation distances:
1.
Mount the wall-mount housing.
2.
Connect the power supply.
3.
Switch on the measuring device.
4.
Run the "Sensor Installation" Quick Setup menu.
Installing the wall-mount transmitter housing
There are various ways of installing the wall-mount housing:
• Direct wall mounting
• Panel mounting (with separate mounting kit, accessories
• Pipe mounting (with separate mounting kit, accessories
"
Caution!
• Make sure that the permitted operating temperature range
(-20 to +60 °C / –4 to +140 °F) is not exceeded at the mounting location. Install the device in a
shady location. Avoid direct sunlight.
• Always install the wall-mount housing in such a way that the cable entries are pointing down.
Direct wall mounting
1.
Drill the holes
17.
2.
Remove the cover of the connection compartment (a).
3.
Push the two securing screws (b) through the appropriate bores (c) in the housing.
– Securing screws (M6): max. Ø 6.5 mm (0.26")
– Screw head: max. Ø 10.5 mm (0.41")
4.
Secure the transmitter housing to the wall as indicated.
5.
Screw the cover of the connection compartment (a) firmly onto the housing.
A0001130
Fig. 10:
Direct wall mounting
a
b
c
c
90 (3.54)
35 (1.38)
192 (7.56)
81.5
(3.2)
mm (inch)