Installation
Proline Prosonic Flow 93 PROFIBUS DP/PA
44
Hauser
A0001117
Fig. 43:
Mounting the sensor
5.
Coat the contact surfaces of the sensors with an even layer of coupling fluid approx. 1 mm
(0.04") thick, going from the groove through the center to the opposite edge.
A0011373
Fig. 44:
Coating the contact surfaces of the sensor with coupling fluid
6.
Insert the sensor into the sensor holder.
7.
Fit the sensor cover on the sensor holder and turn until:
– The sensor cover engages with a click
– The arrows (
Å
/
Æ
"close") are pointing towards one another.
8.
Screw the connecting cable into the individual sensor.
A0011376
Fig. 45:
Connecting the connecting cable
This completes the mounting process. The sensors can now be connected to the transmitter via the
connecting cables
62.