Wiring
Proline Prosonic Flow 93 PROFIBUS DP/PA
70
Hauser
4.3.4
PROFIBUS PA connection diagram
Flexible assignment boards
(order version 93***-***********F and 93***-***********H)
A0014365
Fig. 70:
Connecting the transmitter, cable cross-section: max. 2.5 mm
2
(AWG 14)
a
Connection compartment cover
b
Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L
−
for DC
c
Ground terminal for protective ground
d
Fieldbus cable:
Terminal No. 26: PA + (with reverse polarity protection)
Terminal No. 27: PA – (with reverse polarity protection)
e
Ground terminal for signal cable shield
Observe the following:
– the shielding and grounding of the fieldbus cable
– that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f
Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)
PA (–)
PA (+)
1
2
f
22 23
20 21
24 25 26 27
a
L1 (L+)
N (L–)
c
e
b
b
d
d