5.
Configuration of the Analog Input function blocks 1 to 8:
The measuring device has eight Analog Input function blocks (AI modules) via which the
various measured variables can be cyclically transmitted to the PROFIBUS master (Class 1).
The assignment of a measured variable to the Analog Input function block is shown below
using the example of Analog Input function block 1 (AI module, slot 1).
Using the CHANNEL function (6123), you can determine the measured variable
(e.g. VOLUME FLOW
CHANNEL 1) to be cyclically transmitted to the PROFIBUS master (Class 1):
a. Select BASIC FUNCTION (G)
→
PROFIBUS DP (GBA)
→
FUNCTIONBLOCKS (612)
→
BLOCK SELECTION (6120).
b. Select the option ANALOG INPUT 1.
c. Select the function CHANNEL (6123).
d. Select the option VOLUME FLOW CHANNEL 1.
Possible settings
6.
Setting the measuring mode:
In the function MEASURING MODE (6601), select the flow portions to be measured by the
measuring device.
BASIC FUNCTION (G)
→
SYSTEM PARAMETER (GLA)
→
CONFIGURATION (660)
→
MEASURING MODE (6601)
→
Selection of one of the following options:
– UNIDIRECTIONAL (factory setting) = only the positive flow portions
– BIDIRECTIONAL = the positive and negative flow components
Measured variable
ID for CHANNEL
function
VOLUME FLOW CHANNEL 1 (factory setting AI function block 1)
273
SOUND VELOCITY CHANNEL 1 (factory setting AI function block 2)
293
FLOW VELOCITY CHANNEL 1 (factory setting AI function block 3)
309
VOLUME FLOW CHANNEL 2 (factory setting AI function block 4)
529
SOUND VELOCITY CHANNEL 2 (factory setting AI function block 5)
549
FLOW VELOCITY CHANNEL 2 (factory setting AI function block 6)
565
AVERAGE VOLUME FLOW (factory setting AI function block 7)
567
AVERAGE SOUND VELOCITY (factory setting AI function block 8)
570
SIGNAL STRENGTH CHANNEL 1
310
SIGNAL STRENGTH CHANNEL 2
566
VOLUME FLOW SUM
568
VOLUME FLOW DIFFERENCE
569
AVERAGE FLOW VELOCITY
571
!
Note!
If, when performing the PROFIBUS network configuration, the AI module was integrated in slot 1 to 8, the measured
variable selected in the CHANNEL function for the respective Analog Input function block 1 to 8 is transmitted cyclically
to the PROFIBUS master (Class 1)