Technical data
Proline Prosonic Flow 93 PROFIBUS DP/PA
154
Hauser
10.1.5
Power supply
Measuring unit electrical
connection
Connecting the connecting
cable
Supply voltage
Transmitter
Current output / HART
• 85 to 260 V AC, 45 to 65 Hz
• 20 to 55 V AC, 45 to 65 Hz
• 16 to 62 V DC
Sensor
• Powered by the transmitter
Cable entries
Power supply and signal cables (inputs/outputs)
• Cable entry M20 × 1.5 (8 to 12 mm / 0.31 to 0.47")
• Cable gland for cables, 6 to 12 mm (0.24 to 0.47")
• Thread for cable entry ½" NPT, G ½"
Connecting cable (sensor/transmitter)
Cable gland for one connecting cable (1 × Ø 8 mm) per cable entry
• Cable gland M20 × 1.5
• Thread for cable entry ½" NPT, G ½"
Cable gland for two connecting cables (2 × Ø 4 mm) per cable entry
• Cable gland M20 × 1.5
• Thread for cable entry ½" NPT, G ½"
A0008152
Fig. 102: Cable gland for two connecting cables (2 × Ø 4 mm / 0.16") per cable entry
Cable specifications
Only use the connecting cables supplied by Hauser.
Different versions of the connecting cables are available
Prosonic Flow P
• Cable material:
– Prosonic Flow 93P (DN 50 to 4000 / 2 to 160"): PVC (standard) or
PTFE (for higher temperatures)
– Prosonic Flow 93P (DN 15 to 65 / ½ to 2½"): TPE-V
• Cable length:
– For use in a non-hazardous zone: 5 to 60 m (16.4 to 196.8 ft)
– For use in a hazardous zone: 5 to 30 m (16.4 to 98.4 ft)