Proline Prosonic Flow 93 PROFIBUS DP/PA
Technical data
Hauser
155
Prosonic Flow W
• Cable material made of PVC (standard) or PTFE (for higher temperatures)
• Cable length: 5 to 60 m (16.4 to 196.8 ft)
!
Note!
To ensure correct measuring results, route the connecting cable well clear of electrical machines
and switching elements.
Power consumption
AC: < 18 VA (incl. sensor)
DC: < 10 W (incl. sensor)
Switch-on current
:
• max. 13.5 A (< 50 ms) at 24 V DC
• max. 3 A (< 5 ms) at 260 V AC
Power supply failure
Lasting min. 1 power cycle
HistoROM/T-DAT (Prosonic Flow 93) saves measuring system data if the power supply fails.
Potential equalization
For potential equalization, no special measures are necessary.