Proline Prosonic Flow 93 PROFIBUS DP/PA
Commissioning
Hauser
121
Possible settings
Possible settings
Factory setting
Example:
You want to cyclically transmit the totalized volume flow as totalizer value 1 to the PROFIBUS
master (Class 1) by means of the TOTAL module (slot 7):
BASIC FUNCTION (G)
→
PROFIBUS PA (GCA)
→
TOTALIZER (613)
→
select TOTALIZER (6130): Select TOTALIZER 1, then select CHANNEL (6133) = VOLUME FLOW
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slots 9 to 11) consists of the functions SETTOT and
TOTAL.
With this module combination:
• The totalizer can be controlled via the automation system (SETTOT).
• The totalizer value is transmitted including the status (TOTAL)
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
• 0 = Totalize (factory setting)
• 1 = Reset totalizer (the totalizer value is reset to 0)
• 2 = Accept totalizer preset
!
Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing continues
automatically. The control variable does not have to be changed to 0 again to restart totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the MODETOT
function
Totalizer value/measured variable (channel 1 = active)
ID for CHANNEL function
VOLUME FLOW CHANNEL 1 (factory setting totalizer 1 to 3)
273
OFF
0
Totalizer value/measured variable (channel 1 + channel 2 =
active)
ID for CHANNEL function
VOLUME FLOW CHANNEL 1 (factory setting totalizer 1 to 3)
273
VOLUME FLOW CHANNEL 2
529
AVERAGE VOLUME FLOW
567
VOLUME FLOW SUM
568
VOLUME FLOW DIFFERENCE
569
OFF
0
!
Note!
If, when performing the PROFIBUS network configuration, the module or the function TOTAL was integrated in
slot 9, 10 or 11, the measured variable selected in the CHANNEL function for the totalizers 1 to 3 is transmitted
cyclically to the PROFIBUS master (Class 1).
Module
Totalizer
function block
Totalizer value/measured variable
Unit
ID for
CHANNEL
function
TOTAL (slot 9)
1
VOLUME FLOW CHANNEL 1
m³
273
TOTAL (slot 10)
2
VOLUME FLOW CHANNEL 1
m³
273
TOTAL (slot 11)
3
VOLUME FLOW CHANNEL 1
m³
273