Wiring
Proline Prosonic Flow 93 PROFIBUS DP/PA
66
Hauser
4.3
Connecting the measuring unit
4.3.1
Terminal assignment
Electrical values for:
• Inputs
• Outputs
PROFIBUS DP
"
Caution!
Only certain combinations of submodules (see Table) on the I/O board are permissible. The
individual slots are marked and assigned to the following terminals in the connection compartment
of the transmitter:
• "INPUT / OUTPUT 3" slot = terminals 22 / 23
• "INPUT / OUTPUT 4" slot = terminals 20 / 21
PROFIBUS PA
PROFIBUS PA
Order version
Terminal No. (inputs/outputs)
20 (+) / 21 (–)
Submodule on
slot No. 4
22 (+) / 23 (–)
Submodule on
slot No. 3
24 (+) / 25 (–)
Fixed on I/O board
26 = B (RxD/TxD-P)
27 = A (RxD/TxD-N)
Fixed on I/O board
93***-***********J
-
-
+5V (power supply for ext.
bus terminator)
PROFIBUS DP
93***-***********V
Relay output 2
Relay output 1
Status input
PROFIBUS DP
93***-***********P
Current output
Frequency output
Status input
PROFIBUS DP
Terminal No. (inputs/outputs)
Order version
20 (+) / 21 (–)
22 (+) / 23 (–)
24 (+) / 25 (–)
26 = PA +
1)
27 = PA –
1)
93***-***********F
-
-
-
PROFIBUS PA, Ex i
93***-***********H
-
-
-
PROFIBUS PA
1)
With integrated reverse polarity protection