Commissioning
Proline Prosonic Flow 93 PROFIBUS DP/PA
114
Hauser
6.6.4
Configuration examples with Simatic S7 HW-Konfig
Example 1:
A0008802
Fig. 89:
Complete configuration using the Prosonic Flow 93 GSD file
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):
Slot
sequence
Module
Byte length
input data
Byte length
output data
Description
1
AI
5
–
Analog Input function block 1
Output variable
→
(factory setting)
2
AI
5
–
Analog Input function block 2
Output variable
→
(factory setting)
3
AI
5
–
Analog Input function block 3
Output variable
→
(factory setting)
4
AI
5
–
Analog Input function block 4
Output variable
→
(factory setting)
5
AI
5
–
Analog Input function block 5
Output variable
→
(factory setting)
6
AI
5
–
Analog Input function block 6
Output variable
→
(factory setting)
7
AI
5
–
Analog Input function block 7
Output variable
→
(factory setting)
8
AI
5
–
Analog Input function block 8
Output variable
→
(factory setting)
9
SETTOT_MODETOT_TOTAL
5
2
Totalizer function block 1
TOTAL
→
output variable = totalized mass flow (factory setting)
SETTOT
→
totalizer control
MODETOT
→
totalizer configuration