Operation
Proline Prosonic Flow 93 PROFIBUS DP/PA
84
Hauser
5.6
PROFIBUS DP hardware settings
5.6.1
Configuring the write protection
A jumper on the I/O board provides the means of switching hardware write protection on or off.
When hardware write protection is switched on, it is
not
possible to write to the device functions
via PROFIBUS (acyclic data transmission, e.g. via the operating program "FieldCare")..
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1.
Switch off power supply.
2.
Remove the I/O board.
3.
Configure the hardware write protection accordingly with the aid of the jumpers (see Figure).
4.
Installation is the reverse of the removal procedure.
a0003326
Fig. 79:
Switching write protection on and off with the aid of a jumper on the I/O board
A
Flexible assignment board
B
Permanent assignment board
1
Jumper for switching write protection on and off
1.1
Write protection switched on = it is not possible to write to the device functions via PROFIBUS (acyclic data
transmission, e.g. via the operating program "FieldCare")
1.2
Write protection switched off (factory setting) = it is possible to write to the device functions via PROFIBUS
(acyclic data transmission, e.g. via the operating program "FieldCare")
LED
Overview of LED states:
– Lit continuously
→
Ready for operation
– Not lit
→
Not ready for operation
– Flashing
→
System or process error present
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
IN
PU
T/O
UTP
UT
4
IN
PUT/O
UTPU
T
3
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1.1
1.2
1
LED
A
1.1
1.2
1
B
LED
Содержание Proline Prosonic Flow 93
Страница 2: ......
Страница 168: ...www endress com worldwide BA00076D 06 EN 13 10 71121236 FM SGML6 0 ProMoDo...