Installation
Proline Prosonic Flow 93 PROFIBUS DP/PA
38
Hauser
5.
Loosen the screws of the fixers on the measuring wires and remove the measuring wires from
the mounting bolt.
6.
Fit the sensor holders over the individual mounting bolts and tighten securely with the
retaining nut.
A0001114
Fig. 30:
Mounting the sensor holders
7.
Coat the contact surfaces of the sensors with an even layer of coupling fluid approx. 1 mm
(0.04") thick, going from the groove through the center to the opposite edge.
A0011373
Fig. 31:
Coating the contact surfaces of the sensor with coupling fluid
8.
Insert the sensor into the sensor holder.
9.
Fit the sensor cover on the sensor holder and turn until:
– The sensor cover engages with a click
– The arrows (
Å
/
Æ
"close") are pointing towards one another.
10. Screw the connecting cable into the individual sensor.
A0001115
Fig. 32:
Mounting the sensor and connecting the connecting cable
This completes the mounting process. The sensors can now be connected to the transmitter via the
connecting cables
62.