PROFIBUS DP/PA system integration
6.5.1
Device master file (GSD file)
For PROFIBUS network configuration, the device master file (GSD file) is needed for every bus user
(PROFIBUS slave). The GSD file contains a description of the properties of a PROFIBUS device, such
as supported data transmission rate and number of input and output data.
Before configuration takes place, a decision should be made as to which GSD file should be used to
operate the measuring device in the PROFIBUS DP/PA master system.
The measuring device supports the following GSD files:
• Prosonic Flow 93 GSD file (manufacturer-specific GSD file, complete device functionality)
• PROFIBUS Profile GSD file
Below you will find a detailed description of the GSD files supported.
Prosonic Flow 93 GSD file (manufacturer-specific GSD file, complete device
functionality)
Use this GSD file to access the complete functionality of the measuring device. In this way, device-
specific measured variables and functionalities are thus completely available in the PROFIBUS
master system. An overview of the modules available (input and output data) is contained on the
following pages:
PROFIBUS DP
PROFIBUS PA
GSD file with standard or extended format
The GSD file with either the standard or the extended format must be used depending on the
configuration software used. When installing the GSD file, the GSD file with the extended format
(EH3
x
15xx.gsd) should always be used first.
However, if the installation or the configuration of the measuring device fails with this format, then
use the standard GSD (EH3
_
15xx.gsd). This differentiation is the result of different implementation
of the GSD formats in the master systems. Note the specifications of the configuration software.
Name of the Prosonic Flow 93 GSD file
How to acquire
• Internet (Hauser)
→
www.endress.com
→
Download
• CD-ROM with all GSD files for Hauser devices
→
Order No.: 56003894
Contents of the download file from the Internet and the CD-ROM:
• All Hauser GSD files (standard and extended format)
• Hauser type files
• Hauser bitmap files
• Information on the devices
ID No.
GSD file
Type file
Bitmaps
PROFIBUS DP
1531 (Hex) Extended Format
(recommended):
Standard Format:
EH3x1531.gsd
EH3_1531.gsd
EH_1531.200 EH_1531_d.bmp/.dib
EH_1531_n.bmp/.dib
EH_1531_s.bmp/.dib
PROFIBUS PA
1530 (Hex) Extended Format
(recommended):
Standard Format:
EH3x1530.gsd
EH3_1530.gsd
EH_1530.200 EH_1530_d.bmp/.dib
EH_1530_n.bmp/.dib
EH_1530_s.bmp/.dib