41
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4.14.4 DIN ID control 3
Table 40 . DIN ID Control parameters
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.14.4.1 ID Control DIN
0.1
E.10
0.1
1578
Slot . Board input no.
P1.14.4.2 Controlled ID
0
10000
ID
0
1579
Select ID that is controlled by digital input
P1.14.4.3 False value
–32000
32000
0
1594
Value when DI is low
P1.14.4.4 True value
–32000
32000
0
1596
Value when DI is high
4.14.5 ID Controlled digital output 1
Table 41 . ID Controlled digital output parameters, G1 .14 .5
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.14.5.1 ID.Bit free DO
0.00
2000.15
ID.Bit
0.00
1216
P1.14.5.2 Free DO Sel
0.1
E.10
0.1
1574
4.14.6 ID Controlled digital output 2
Table 42 . ID Controlled digital output parameters, G1 .14 .6
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.14.6.1 ID.Bit free DO
0.00
2000.15
ID.Bit
0.00
1386
P1.14.6.2 Free DO Sel
0.1
E.10
0.1
1325
4.14.7 Free DIN delay
Table 43 . ID Controlled digital output parameters, G1 .14 .7
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.14.7.1 ID.Bit free DIN
0.00
2000.15
ID.Bit
0.00
1832
P1.14.7.2 On delay
0.00
320.00
s
0.00
1833
P1.14.7.3 Off delay
0.00
320.00
s
0.00
1834
P1.14.7.4 Mono time
0.00
320.00
s
0.00
1836
P1.14.7.5 Control out ID
0
10000
0
1835
4.15 Brake control
Table 44 . Brake control parameters, G1 .15
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.15.1
BrakeMechDelay
0.00
320.00
s
0.00
1544
Time that is required to open the brake
P1.15.2
Brake OFF FreqLim open loop 0.00
320.00
Hz
1.50
1535
Opening limit and maximum reference limit when brake is closed.
P1.15.3
Brake OFF FreqLim closed
loop
0.00
320.00
Hz
0.00
1555
Opening limit and maximum reference limit when brake is closed.
P1.15.4
Brake ON F
0.00
320.00
Hz
1.00
1539
Close frequency from positive direction
P1.15.5
Brake ON FreqLim -
0.00
320.00
Hz
1.50
1540
Close frequency from negative direction
P1.15.6
Brake On/Off current limit
0.00
320.00
A
0.00
1085
Brake is closed immediately id current goes below this value.
P1.15.7
Generator torque limit
increase speed level
0.00
320.00
Hz
0.00
1547
Function disabled when zero. Point where Generator torque limit stars
to increase.
P1.15.8
Generator torque limit
increase maximum speed limit
0.00
320.00
Hz
100.00
1548
Point where torque value of ID1549 is added to base generator
torque limit.
P1.15.9
Generator torque limit
increase maximum addition
0.0
300.0
%
300.0
1549
P1.15.10
Brake fault action
1
3
1
1316
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P1.15.11
Brake fault delay
0.00
320.00
s
0.20
1317