37
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4.12.4 Speed error monitoring
Table 29 . Speed error monitoring
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.4.1 Speed error mode
0
3
0
752
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P1.12.4.2 Speed error limit
0.0
100.0
%
5.0
753
P1.12.4.3 Speed fault delay
0.00
100.00
S
0.1
754
4.12.5 Motor thermal protections
Table 30 . Motor thermal protections
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.5.1 Thermal protection of
the motor
0
3
2
704
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P1.12.5.2 Motor ambient
temperature factor
–100.0
100.0
%
0.0
705
P1.12.5.3 Motor cooling factor at
zero speed
0.0
150.0
%
40.0
706
P1.12.5.4 Motor thermal time constant
1
200
min
45
707
P1.12.5.5 Motor duty cycle
0
100
%
100
708
P1.12.5.6 Response to thermistor fault
0
3
2
732
See P1.12.5.1
P1.12.5.7 Over load response
0
2
1
1838
0=No response
1=Warning
2=Fault
P1.12.5.8 Over Load Signal
0
2
0
1837
0=Not Used
1=Current
2=Torque
3=Power
P1.12.5.9 Over load maximum input
0.0
300.0
%
150.0
1839
P1.12.5.10 Over load maximum step
0
10000
200
1840
4.12.6 4mA Protection
Table 31 . 4mA Protection
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.12.6.1 Response to 4mA
reference fault
0
5
0
700
0=No response
1=Warning
2=Previous Freq.
3=Wrng+PresetFreq 2.12.6.2
4=Fault,stop acc. to 2.3.2
5=Fault,stop by coasting
P1.12.6.2 4mA reference fault
frequency
0.00
P1.1.2
Hz
0.00
728