131
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Description
Notes
P1 .11 .6
1093
Master Follower mode 2 selection “MF mode 2”
4 = “DSynchFlwr” - Drive Synch Follower
Selection for parallel drive configuration follower drive
P1.11.7
11082
SystemBus communication fault response “SB comm fault”
Defines the action when the System Bus heartbeat is missing. The master drive sends
a heartbeat signal to all follower drives and this heartbeat is sent back to the master
drive.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop function
3 = Fault, stop mode after fault always by coasting
P1.11.8
1352
Systembus fault delay ID1352 “SB fault delay”
Defines the delay before fault generation when heartbeat is missing.
P1.11.9
1536
Follower fault “follower fault”
Defines the response in the Master drive when a fault occurs in any of the follower
drives. When one of the drives trips to fault the master drive will send a command to
trigger the Data Logger in all the drives for diagnostic purposes.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop function
When follower reference selection
is 17 = “Master
Ref”, speed limitation function
from brake control are
bypassed on follower side.
Code
ID
Description
Notes
P1.11.10.1
1531
DriveSynch follower fault “DS follower fault”
Defines the response in the Master drive when a fault occurs in any of the follower
drives. When one of the drives trips to fault the master drive will send a command to
trigger the Data Logger in all the drives for diagnostic purposes.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop function
P1.11.10.2
1518
Follower drive winding phase shift “FollPhaseShift”
Windings phase shift between master and follower drive. Used with drive synch
operation when the motor has multiple windings.
P1.11.10.3
519
DC voltage balancing gain “DCVoltageBalGain”
Multiple wind motor option. Contact factory before changing this value.
P1.11.10.4
1799
SB last ID 2nd “SBLastID 2nd”
With this parameter is possible to change last ID number of the drive from fieldbus.
Code
ID
Description
Notes
P1.12.1.1
730
Input phase supervision “input ph. superv”
Defines the response when the drive notices that one of the input phases is missing.
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop Function
3 = Fault, stop mode after fault always by coasting
4 = Warning and Derate – This mode will derate the drive to the level defined in
P1.12.1.
P1.12.1.2
748
Phase loss derate % “PHLoss derate%”
The current limit will be multipled by this % to limit current when a phase loss occurs.
5.12.3.1 Drive synch control parameters
5.13 Protections
5.13.1 General settings