SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
5.4.2.1 Forced control place
Digital inputs can be used to bypass parameter P2.1 Control Place,
when P2.1 is set to either keypad select or IO select.
Priority is:
1 – Force Local
2 – Force Remote 2
3 – Force Remote 1
Code
ID
Parameter
Notes
P1.4.2.18
409
Force local “Force local”
Contact closed: Force control place to Local
P1.4.2.19
410
Force Remote 1 “Force remote 1”
Contact closed: Force control place to Remote 1
P1.4.2.20
411
Force Remote 2 “force remote 2”
Contact closed: Force control place to Remote 2
When the control place is forced
to change the values of Start/
Stop, Direction and Reference
valid in the respective control
place are used. The value of
parameter ID125 (Keypad Control
Place) does not change. When
the input opens the control place
is selected acording to keypad
control parameter P3.1 Control
Place
P1.4.2.21
496
Parameter Set 1/Set 2 selection “param set1/set2”
With this parameter you can select between Parameter Set 1 and Set 2.
Remember to put same input for both parameter set. Parameter sets cannot be
changed while drive is in run state.
Digital input = FALSE:
•
Set 1 is loaded as the active set
Digital input = TRUE:
•
The active set is saved to set 1
When making two parameter sets from the keypad
1. Set all parameters as needed for SET1
2. In “P6.3.1 Parameter Set” select “Store Set1”
3. Set all parameters as needed for SET 1
4. In “P6.3.1 Parameter Set” select “Store Set2”
Active Set shown in Status Word B9
The parameter values are stored
only when selecting parameter
P6.3.1 Parameter sets Store Set 1
or Store Set 2 or from 9000xDrive:
Drive > Parameter Sets.
P1.4.2.22
164
Motor control mode 1/2“Mot ctrl mode1/2”
This digital input is used to change between to motor control mode
selection parameters:
•
P1.8.1 Motor Ctrl Mode ID600
•
P1.8.2 Motor Ctrl Mode2 ID521
Contact is open = Motor control mode 1 is selected
Contact is closed = Motor control mode 2 is selected
When changing between open loop and closed loop control modes, make this change
in stop state.
P1.4.2.23
210
External brake acknowledgment. “Ext. brake ACK”
Connect this input signal to auxiliary contact of mechanical brake. If contact is not
closed within given time when brake is controlled open the drive will generate a brake
fault F58, response can be selected in G2.14 Brake Control parameter group.
P1.4.2.24
750
Cooling monitor “Cooling monitor”
When using a liquid-cooled drive or CPX, connect this input to the Cooling OK signal
from flow control application or any input that shows state of used cooling unit. See
details of operation from G2.11.9 cooling parameters group.