71
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.4.2.34
1092
Master Follower mode 2 “MF mode 2”
Master Follower mode can be changed with digital input between P1.10.1 MF Mode
and P1.10.5: MF Mode 2 in the Master Follower parameter group. This can be used for
redundancy purposes e.g. when using a Drive Synch system.
MF Mode 2
MF Mode 1
MF Mode 2
G
IN 0
IN 1
SEL
Used MF Mode
DI
P
P
P1.4.2.35
1213
Quick stop “Quick stop”
Digital input for Quick Stop function
P1.4.2.36
1624
Motoring torque limit 1 “Mot. torq. limit 1”
Digital input for activating motoring torque limit 1
P1.4.2.37
1626
Generator torque limit 1 “Gen. torq. limit 1”
Digital input for activation generator torque limit 1
P1.4.2.38
1753
Store parameters “Store param. Set”
Stores active set to currently selected parameters set. Selection is done by “Param.
Set1/Set2” digital input that is also used to load parameter set to active set.
P1.4.2.39
403
Start signal 1B “Start signal 1B”
Signal selection 1B for the start/stop logic.
This is for Start Place B, selected with P1.4.2.39
Default programming 0.1.Default Forward start, selected with P1.4.1.1
P1.4.2.40
404
Start signal 2B “Start signal 2B”
Signal selection 2B for the start/stop logic.
This is for Start Place B, selected with P1.4.2.39
Default programming 0.1. Default Reverse start, selected with P1.4.1.1.
P1.4.2.41
1896
RR enable “RR enable”
Run Request Enable command.
P1.4.2.42
1600
Output contactor interlock “O/P interlock”
If contact is open 250ms after run command is given the drive will fault based on the
setting of P1.12.1.7
P1.4.2.43
1601
PID set point 1/2 select “PID SP 1/2 sel”
Run Request Enable command.
5.4.3 Analog input 1 & 2
P
AI1-2 Signal Sel
IN OUT
AN.IN
SCALING
OUT
Out_Max
In_Min
Out_Min
In_Max
IN
P
Signal Range
100 %
MUX
K
IN 0
IN 1
IN 2
IN 3
100 %
100 %
P
AIx Custom Max
0 %
20 %
0 %
MUX
K
IN 0
IN 1
IN 2
IN 3
P
AIx Custom Min
P
AIx RefScale Max
SEL
G
IN 0
IN 1
NE
IN 1
IN 2
0
P
Max Frequency
SEL
G
IN 0
IN 1
0
P
AIx RefScale Min
A
AI2_Ref
A
AI1_Ref