160
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
8. Status and control word in detail
Combination
P7.x.1.4
Operate Mode
P1.13.22
State machine
1
1/ProfiDrive
1/Basic
Control and status word are explained in fieldbus option board manual
2
2/ByPass
Some fieldbus board operate by
default in “ByPass” mode
2/ProfiDrive
Control word is ProfiDrive type and explained in this manual.
Status Word is can be selected by ID number, default is ProfiDrive type ID65
V7.26.2 FB Status Word
3
2/ByPass
1/Basic
Control word is “Three Bit” control.
Status Word is can be selected by ID number, default is ProfiDrive type ID65
V7.26.2 FB Status Word
4
1/ProfiDrive
2/ProfiDrive
Drive cannot be operated in this combination from fieldbus.
8.1 Combination 1, ProfiDrive – standard with profibus option board
8.1.1 Control word combination 1, ProfiDrive – basic with profibus option board
Main Control Word for Profibus in Combination 1
False
True
Comment
b0
STOP 1 (by ramp)
ON 1
Keep this TRUE
b1
STOP 2 (by cost)
ON 2
Keep this TRUE
b2
STOP 3 (by ramp)
ON 3
Keep this TRUE
b3
RUN DISABLE
ENABLE
Use this for start and stop command
b4
No Action
START
Keep this TRUE
b5
No Action
START
Keep this TRUE
b6
No Action
START
Keep this TRUE
b7
No Action
Fault Reset 0 > 1
Use this for fault reset
b8
No Action
No Action
Not used
b9
No Action
No Action
Not used
b10
Disable profibus control
Enable fieldbus control
See profibus manual
b11
Fieldbus DIN1=OFF
Fieldbus DIN1=ON
See P1.5.1.17 -18
b12
Fieldbus DIN2=OFF
Fieldbus DIN2=ON
See P1.5.1.19 -20
b13
Fieldbus DIN3=OFF
Fieldbus DIN3=ON
See P1.5.1.21 -22
b14
Fieldbus DIN4=OFF
Fieldbus DIN4=ON
See P1.5.1.23 -24
b15
Fieldbus DIN5=OFF
Fieldbus DIN5=ON
Not used
8.1.2 Status word combination 1, ProfiDrive – basic with profibus option board
Main Status Word for Profibus in Combination 1
False
True
Comment
b0
Not ready (initial)
READY 1 (SM)
See profibus manual
b1
Not Ready
READY 2 (SM)
See profibus manual
b2
DISABLE
ENABLE (SM)
See profibus manual
b3
NO FAULT
FAULT ACTIVE
Directly from the drive
b4
STOP 2
NO STOP 2 (SM)
See profibus manual
b5
STOP 3
NO STOP 3 (SM)
See profibus manual
b6
START ENABLE
START DISABLE (SM)
See profibus manual
b7
No warning
Warning
Directly from the drive
b8
Reference ≠ Actual value
Reference = Actual value
b9
Fielbus control OFF
Fielbus control ON
See profibus manual
b10
Not used
Not used
b11
Not used
Not used
b12
FC Stopped
Running
Directly from the drive
b13
FC not ready
Ready
Directly from the drive
b14
Not used
Not used
b15
Not used
Not used
SM = Profibus board State Machine