SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.17.1.4 Engineering unit
0
10
0
1795
0=%
1=degF
2=degC
3=psig
4=Bar
5=Feet
6=in water col
7=GPM
8=ft/min
9=CFM
10=PPM
P1.17.1.5 PID Min limit
–32768
P1.17.1.6
0
359
P1.17.1.6 PID Max limit
P1.17.1.5 32767
100.00
360
P1.17.1.7 Error inversion
0
1
0
342
0=Not Inverted
1=Inverted
4.17.2 PID Set points
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.17.2.1 PID Set point source
0
1
0
332
0=Source 1
1=Source 2
P1.17.2.2 PID Source 1 select
0
4
2
334
0=AI1
1=AI2
2=Keypad PID ref 1
3=Fieldbus PD1
4=Motor potentiometer
P1.17.2.3 PID Source 2 select
0
4
3
335
See P1.17.2.2
R1.17.2.4 Keypad PID Reference 1
P1.17.2.5 P1.17.2.6 P1.17.1.4 50.0
P1.17.2.5 Keypad PID Set point 1 Min
P1.17.1.5 P1.17.1.6 P1.17.1.4 0
361
P1.17.2.6 Keypad PID Set point 1 Max P1.17.1.5 P1.17.1.6 P1.17.1.4 100.00
362
R1.17.2.7 Keypad PID Reference 2
P1.17.2.8 P1.17.2.9 P1.17.1.4 50.0
P1.17.2.8 Keypad PID Set point 2 Min
P1.17.1.5 P1.17.1.6 P1.17.1.4 0
363
P1.17.2.9 Keypad PID Set point 2 Max P1.17.1.5 P1.17.1.6 P1.17.1.4 100.00
364
P1.17.2.10 PID Reference rise time
.1
100.0
s
.1
343
P1.17.2.11 PID Reference fall time
.1
100.0
s
.1
344
P1.17.2.12 PID Sum point reference
0
6
0
376
0=Direct
1=AI1
2=AI2
3=AI3
4=AI4
5=Keypad SP1
6=Fieldbus PDI3
4.17.3 PID Feedbacks
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.17.3.1 Function
0
7
0
333
0=Source 1
1=Source 1 + Source 2
2=Source 1 - Source 2
3=Source 1 * Source 2
4=Min(Source1,Source2)
5=Max(Source1,Source2)
6=Mean(Source1,Source2)
7=Sqrt(Sqrt(Source2)