SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.4.1.1
300
7 “StrtR-Enable” – Start command rising edge – Run Enable
DIN1: closed contact = start (Rising edge required to start)
Open contact = stop
DIN2: closed contact = start enabled
Open contact = start disabled and drive stopped if running
8 “RPuls-RPuls” – Start rising edge – Stop rising edge
DIN1: closed contact = Start (Rising edge required to start)
DIN2: closed contact = Stop (Rising edge required to stop)
Code
ID
Parameter
Notes
P1.4.2.1
403
Start signal 1 “Start signal 1”
Signal selection 1 for the start/stop logic.
This is for Start Place A, selected with P1.4.1.1
Default programming A.1.Default Forward start.
P1.4.2.2
404
Start signal 2 “start signal 2”
Signal selection 2 for the start/stop logic.
This is for Start Place A, selected with P1.4.1.1
Default programming A.2. Default Reverse start.
P1.4.2.3
407
Run enable “run enable”
When run enable is removed from the drive coasting stop is made always.
Drive will
also show warning indication when run is disabled.
Contact open: Start of motor disabled
Contact closed: Start of motor enabled
P1.4.2.4
412
Reverse “reverse”
This reverse command is active when Start signal 2 is not used for reverse command
because setting of “Start/Stop logic selection” parameter.
Contact open: Direction forward
Contact closed: Direction reverse
P1.4.2.5
419
Preset speed 1 “preset speed 1”
P1.4.2.6
420
Preset speed 2 “preset speed 2”
P1.4.2.7
421
Preset speed 3 “preset speed 3”
Digital input selections for activating preset speeds.
References are set in the “Constant Reference” parameter group.
Table 51.
Speed
Digital input
preset speed 1
Digital input
preset speed 2
Digital input
preset speed 3
Basic speed
0
0
0
Preset speed 1
1
0
0
Preset speed 2
0
1
0
Preset speed 3
1
1
0
Preset speed 4
0
0
1
Preset speed 5
1
0
1
Preset speed 6
0
1
1
Preset speed 7
1
1
1
Related parameters - G1.2.7 Constant Ref
5.4.2 Digital inputs