19
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4.2.8 Adjust reference
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.2.12.1 Adjust input
0
5
0
493
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=Fieldbus
P1.2.12.1 Adjust minimum
0.0
100.0
%
0.0
494
Adjust limit to decrease ref.
P1.2.12.1 Adjust maximum
0.0
100.0
%
0.0
495
Adjust limit to increase ref.
4.3 Ramp control
4.3.1 Basic settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.3.1
Start function
0
1
0
505
0=Ramp
1=Flying start
P1.3.2
Stop function
0
1
0
506
0=Coasting
1=Ramp
P1.3.3
Acceleration time 1
0.2
3270.0
s
3.0
103
0 Hz to Max frequency
P1.3.4
Deceleration time 1
0.2
3270.0
s
3.0
104
Max frequency to 0 Hz
P1.3.5
Ramp 1 shape
0
100
%
2
500
0=Linear
>0=S-curve ramp time
P1.3.6
Acceleration time 2
0.2
3270.0
s
10.0
502
P1.3.7
Deceleration time 2
0.2
3270.0
s
10.0
503
P1.3.8
Ramp 2 shape
0
100
%
4
501
0=Linear
>0=S-curve ramp time
P1.3.9
Inching ramp
0.01
320.00
s
1.00
1257
P1.3.10
Reducing of acc./dec. times 0
5
0
401
Scales active ramp from 100 % to 10 %.
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=Fieldbus
4.3.2 Quick stop
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.3.11.1 IO Quick stop mode
0
1
0
1276
0=Coasting
1=Ramp
P1.3.11.2 Quick stop ramp time
0.1
3200.0
s
1256
4.3.3 Ramp control options
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.3.12.1 Ramp: Skip S2
0
1
0
1900
P1.3.12.2 CL Ramp follower encoder
frequency
0
1
0
1902
P1.3.12.3 Ramp input interpolator TC
0
200
ms
10
1184